Applications
|
Characteristics
|
These heating cables are mainly used as heat tracing tools to stabilise temperature of liquid transferring pipes and liquids in manay industrial facilities like thermal power plants, chemical plants, etc. These cables are the most important part of the heat tracing systems. They also can be used safely to prevent moisture and icing from cooling systems.
|
PRODUCT CODE :535
KS: Silicone insulated core, silicone outer sheath cuttable heating cable |
Technical Details
|
KS
|
Conductor Diameter:
|
2x0,75 mm² Nickel-Copper
|
Heating Wire:
|
Nickel Chrome or Nickel Copper
|
Outer Diameter:
|
5,00 mm x 7,00 mm
|
Max. Ohm.:
|
---
|
Max. Voltage:
|
220 - 230 V
|
Max. Power(wattage):
|
20 w/m --> 60 w/m
|
Max. Working Temperature:
|
-70°C / +200°C
|
Tolerance:
|
Resistance: ± %10
Diameter: ±0,2 mm
Length:± %1
|
Ending Insulation:
|
Shiring Tube or Silicone Ending Piece
|
Max. Circuit Length:
|
40 - 80 meter
|